Radiator balancing valve serves for the installation setting of the calculated flow rate of the coolant through the heating devices of water heating systems, as well as for disconnecting the heater from the network. Valve can be used on the pipelines of potable and domestic use, hot water supply systems, as well as on technological pipelines transporting liquids which are not aggressive to the materials of the valve. A half-coupling allows the valve to be assembled and disassembled without dismantling the pipeline. Brass plug protects the valve against unauthorized interference with the installation setting.

Dimensions, G 1/2” × 1/2”
A × B, mm 50,5 × 46,5
Working pressure, bar up to 10
Maximum pressure, bar 15
Flow rate through a closed valve at a pressure difference of 1 kPa, cm3/min 0 ÷ 5
Torque at standard hexagonal key, N·m Maximum 2,0
Number of full turns of setting plunger, revolution 3
Mounting position any
Allowed bending moment on the valve body, N·m up to 100
Temperature range of operating medium, ℃ 0 ÷ +130
Permissible ambient temperature, ℃ +5 ÷ +55
Permissible % relative humidity of the environment up to 80
Axle bolt hexagon 8
Body material Brass CW617N chrome plated